Pharmaspecs

Equipment Installation Qualification checklist

The equipment installation Qualification checklist is the tests performed during IQ, which prove equipment installation according to the design requirements and manufacturer’s recommendation. Let’s discuss what to include in an Installation Qualification checklist.

 

Equipment Installation Qualification is part of equipment validation activity, performed after the equipment is installed. It consists of an equipment installation qualification checklist that verifies the equipment’s installation according to the design and manufacturer’s recommendation

It provides documented evidence that the pharmaceutical equipment is installed according to the equipment’s design requirements and the manufacturer’s recommendation. Additionally, after installation, the equipment will operate and perform as per the buyer’s requirements.

These requirements and recommendations are thoroughly discussed during the design qualification phase.

Equipment Installation Qualification template

The equipment installation template is the format used to record all tests during the Installation qualification activity. It presents a checklist sequence, followed by personnel during the IQ activity.

There are no strict rules and regulations for designing installation qualification template, and it mainly depends on the manufacturer and the buyer’s decision. However, a typical installation qualification template consists of a test description, its acceptance criteria, and the actual result.

Tests are written in tabular form, with their corresponding acceptance criteria, actual value, and result, i.e., Pass or Fail.

When a particular set of tests have been conducted, the person conducting the IQ signs it, and the quality person approves the test by its signature.

The common Installation Qualification format is mentioned below.

Installation qualification template is the format used to record tests during Installation qualification activity

 

In the above template, below is the explanation of each column

Equipment Installation Qualification Checklist

Installation Qualification checklist is a series of tests performed related to equipment installation. Before conducting Installation Qualification, the manufacturer prepares the desired IQ checklists in an approved format. These checklists are then sent to the buyer for their review and approval. When both the manufacturer and buyer approve the test format, the Installation Qualification checklist becomes official.

Installation qualification checklist

Let’s look at common tests routinely performed in an Installation Qualification activity.

Elements of Installation Qualification

Design Characteristics

It includes tests related to the design attributes of the equipment being installed. It ensures that all the attached components are installed according to the agreed characteristics.

Let’s look at some design characteristics tests and their acceptance criteria.

S.No Test Acceptance Criteria Result PASS / FAIL
1 Material of construction

 

Piping

Exhaust

Electrical Conduit

Pneumatic Conduit

Duct

 

 

SS / MS / Insulation

MS

SS / MS

SS / MS

SS / MS

2 Area of Installation The area must be free from dust and particles
3 Ventilation There must be adequate arrangements of ventilation in area
4 Foundation The equipment foundation must be solid and rigid
5 Space for person movement Adequate space for the operator and another personnel movement must be provided
6 Space for material Adequate space for placing different material must be provided
7 Electrical safety The electrical supply must be properly provided with relevant safety system
8 Compressed Air The compressed air must be supplied with adequate pneumatic components and safety system
9 Steam Line The steam line must be proper with adequate components and safety system

 

Utility Requirements

This section verifies that the utilities provided are according to the equipment requirements, as agreed during the design qualification phase.

Every pharma equipment requires standard utility supplies for its satisfactory performance. The equipment will not operate according to design specifications if these are not provided.

Some tests common in this section are mentioned below.

S.No Test Acceptance Criteria Result PASS / FAIL
1 Electricity The electrical supply must be

·         380V/220 VAC

·         3 phase / single phase

2 Steam The steam pressure must be _____ bar / psi
3 Compressed Air The compressed air must be ___bar / psi.

 

The compressed air must be dry, free from water.

4 Natural gas The natural gas pressure must be——– bar / psi.
5 Chilled Water The chilled water supply must be ——– bar / psi, at ——–⁰C
6 Purified Water The purified water supply must be ——– bar / psi.
7 Water for Injection The water for injection supply must be ——– bar / psi.

 

 Documentation

During the design qualification phase, the buyer mentions the documentation they require, which becomes mandatory for the manufacturer to supply with equipment.

In this test, the buyer checks and verifies all the required documentation that the manufacturer has supplied with the equipment.

Some common tests performed in this section include the following.

S.No. Test Acceptance Criteria Result PASS / FAIL
1 Operation Manual Operational manual with detailed guidelines should be supplied
2 Wiring Diagram Wiring diagram with detailed guidelines should be supplied
3 Maintenance manual Maintenance manual, containing  schedule with detailed guidelines should be supplied
4 Validation documents (including DQ, IQ, OQ and PQ) Manufacturer must provide following Validation documents

IQ

OQ

PQ

5 Preventive Maintenance Manual Manufacturer must provide Preventive maintenance procedure with complete schedule
6 Calibration Manufacturer must provide calibration procedure of all measuring instrument and devices with detailed schedule.
7 Spare parts list Manufacturer must provide spare parts list of all the critical items and components.

Certificates

This test includes verification that the desired certificates are provided with the machine, agreed upon during the design qualification stage.

Certificates are necessary because the pharma process are critical and requires specialized materials, devices, and instruments. To ensure that the manufacturer has adequately applied all requirements, the manufacturer provides certificates as proof. Additionally, regulatory authorities such as the United States FDA can review them during their routine inspection.

Some common tests performed in this section include the following

S.No Test Acceptance Criteria Result PASS / FAIL
1 Calibration certificates Calibration certificates for all the recording and measuring devices must be provided

 

The certificates must not be expired

2 Material of construction

 

 

 

Certificates for material of construction of specific machine parts must be

Product contact parts must  be SS 316L

Non contact parts must be SS 304

 Environmental Conditions

In this section, environmental condition equipment is checked and verified.

Pharmaceutical equipment require specific conditions for their satisfactory performance. If the desired environmental conditions are not provided, it will negatively impact the output product and equipment performance.

Some common tests performed in this section include the following.

S.No Test Acceptance Criteria Result PASS / FAIL
1 Area Temperature The temperature must be—– ⁰C
2 Area Humidity The area humidity must be ——–
4 Laminar Flow Laminar air flow with —– air speed must be installed
5 Air Changes Air changes in the area must be —-
 6 Differential Pressure Differential pressure of the area must be——-

The pressure in the areas must be negative / positive

Area Classification The area for production must be ___ (Class A , B , C , D)

 

 

Exit mobile version